问题1.
1.照明回路WL1:
(1)钢管SC20 工程量计算:
(4.4-1.5-0.45+0.05)+1.9+(4+4)×3+3.2(5 根)+3.2+1.10(6 根)+(4.4-1.3+0.05)(6 根)=39.05(m)上式中未标注的管内穿4 根线
(2)钢管SC15(穿3 根)工程量计算:0.9+(3-1.3+0.05)=2.65(m)
(3)管内穿2.5mm
2 线:
(0.3+0.45)×4 +[(4.4-1.5-0.45+0.05)+1.9+(4+4)×3+3.2] ×4+ 3.2×5+[1.10+(4.4-1.3+0.05)]×6+ [0.9+(3-1.3+0.05)]×3=3+126.4+16+25.5+7.95=178.85 (m)
2.照明回路WL2:
(1)钢管SC20 工程量计算:
(4.4-1.5-0.45+0.05)+14.5+(4+4)×3+3.2(5 根)+3.2+0.8(6 根)+(4.4-1.3+0.05)(6 根)=51.35(m)上式中未标注的管内穿4 根线
(2)钢管SC15(穿3 根)工程量计算:1.3+(3.4-1.3+0.05)=3.45(m)
(3)管内穿2.5mm
2 线:
(0.3+0.45)×4 +[(4.4-1.5-0.45+0.05)+14.5+(4+4)×3+3.2] ×4+ 3.2×5+[0.8+(4.4-1.3+0.05)]×6+ [1.3+(3.4-1.3+0.05)]×3=3+176.8+816+23.7+10.3516.35=229.85(m)
3.插座回路WX1:
(1)钢管SC15 工程量计算:
(1.5+0.05)+6.3+(0.05+0.3)×3+6.4+(0.05+0.3)×2+7.17+(0.05+0.3)+7.3+(0.05+0.3)×2+6.4+(0.05+0.3)×2+7.17+(0.05+0.3)=46.14(m)或者(1.5+0.05)+6.3+7.3+(6.4+7.17)×2+(0.05+0.3)×11=46.14(m)
(2)管内穿2.5mm
2 线:
( 0.3+0.45)×3 +[( 1.5+0.05) +6.3+7.3+ ( 6.4+7.17)×2+ ( 0.05+0.3)×11] ×3=2.25+138.24=140.67(m)
照明和插座回路的钢管SC20 合计:39.05+51.35=90.40(m)
照明和插座回路的钢管SC15 合计:2.65+3.45+46.14=52.24(m)
管内穿线BV2.5mm
2 合计:178.85+229.85+140.67=549.37(m)
4.避雷网工程量:
沿支架明敷[24.2×2+8.4×2+(5.1-4.5)×2] ×(1+3.9%)=68.99(m)
沿混凝土支墩明敷8.4 ×(1+3.9%)=8.73(m)
5.均压环工程量:
24.2×2+8.4×2=65.2(m)
问题2:
综合单价分析表见表6-Ⅲ-4。